Ethernet I/O Module with 2-port Ethernet Switch, 10-ch Thermocouple Input, 3-ch DO
The ET-7218Z series modules are designed for high-precision thermocouple measurement. Each input channel provides automatic cold-junction compensation to ensure consistent and stable temperature readings in the field.The modules include open thermocouple detection as well as EMS (EFT/ESD/Surge) protection. In addition to supporting multiple thermocouple input types, every input channel can also be individually configured for current or voltage input, delivering optimal flexibility for a wide range of application requirements. This series also offers digital output channels, each equipped with short-circuit and overload protection.
| Analog Input | |||||||
|---|---|---|---|---|---|---|---|
| Model | AI | DO | |||||
| Channel | Voltage & Current Input | Sensor Input | Channel | Type | Sink/Source (NPN/PNP) | ||
| ET-7005 | – | 8 | – | Thermistor | 4 | Open Collector | Sink (NPN) |
| PET-7005 | – | ||||||
| ET-7015 | ET-7215 | 7 | – | RTD: Pt100, Pt1000, Ni120, Cu100, Cu1000 |
– | – | – |
| PET-7015 | PET-7215 | ||||||
| ET-7017 | ET-7217 | 8 |
±150 mV, ±500 mV, ±1 V, ±5 V, ±10 V, ±20 mA, 0~20 mA, 4~20 mA |
– | 4 | Open Collector | Sink (NPN) |
| PET-7017 | PET-7217 | ||||||
| ET-7017-10 | ET-7217-10 | 10/20 |
±150 mV, ±500 mV, ±1 V, ±5 V, ±10 V, ±20 mA, 0~20 mA, 4~20 mA |
– | – | – | – |
| PET-7017-10 | PET-7217-10 | ||||||
| – | ET-7217-A5 | 8 | ±50 V, ±150 V | – | 4 | Open Collector | Sink (NPN) |
| – | PET-7217-A5 | ||||||
| – | ET-7217RMS | 8 |
0~+10 Vrms, 0~+5 Vrms, 0~+1 Vrms, 0~+500 mVrms, 0~+150 mVrms |
– | 4 | Open Collector | Sink (NPN) |
| – | PET-7217RMS | ||||||
|
Note 1: We recommend ET-7018Z / PET-7018Z and ET-7019Z / PET-7019Z for highly accurate thermocouple measurement. Note 2: 6 DO channels for ET-7018Z, PET-7018Z, ET-7019Z, PET-7019Z. 3 DO channels for ET-7218Z, PET-7218Z, ET-7219Z, PET-7219Z. |
|||||||
| Software | |
|---|---|
| Built-in Web Server | Yes |
| CPU Module | |
|---|---|
| Watchdog Timer | Module, Communication (Programmable) |
| Isolation | |
|---|---|
| 2-way Isolation |
Ethernet: 1500 VDC I/O: 2500 VDC |
| EMS Protection | |
|---|---|
| EFT (IEC 61000-4-4) | ±4 kV for Power Line |
| ESD (IEC 61000-4-2) |
±4 kV Contact for Each Terminal ±8 kV Air for Random Point |
| LED Indicators | |
|---|---|
| Status | Run, Ethernet, I/O |
| Analog Input | |
|---|---|
| Channels | 10 (Differential) |
| Type |
Thermocouple Voltage Current |
| Stable and Consistent Temperature Output | Yes |
| Range |
Thermocouple (J, K, T, E, R, S, B, N, C, L, M, and LDIN43710) ±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, ±2.5 V ±20 mA, 0 ~ 20 mA, 4 ~ 20 mA (Requires Optional External 125 Ω Resistor) |
| Resolution | 16-bit |
| Accuracy | ±0.1% of FSR or better |
| Sampling Rate | 10 Hz (total channels) |
| Input Impedance | >300 kΩ |
| Overvoltage Protection | 240 Vrms |
| Individual Channel Configuration | Yes |
| Open Wire Detection | Yes |
| Isolation | ±400 VDC, Virtual Channel-to-Channel Isolation |
| Ethernet | |
|---|---|
| Ports | 2 × RJ-45, 10/100 Base-TX, Switch Ports |
| LAN Bypass | Yes |
| Access Control | ID, Password and IP Filter |
| Protocol | Modbus TCP, Modbus UDP |
| Power | |
|---|---|
| Reverse Polarity Protection | Yes |
| Consumption | 3.1 W (max.) |
| Powered from Terminal Block | +12 ~ +48 VDC |
| Mechanical | |
|---|---|
| Dimensions (mm) | 76 × 120 × 42 (W × L × H) |
| Installation | DIN-Rail mounting |
| Environment | |
|---|---|
| Operating Temperature | -25 ~ +75 °C |
| Storage Temperature | -30 ~ +80 °C |
| Humidity | 10 ~ 90% RH, Non-condensing |