iSN-101/S2

iSN-101/S2

1-channel Liquid Leak Detection Module with cables

Features

  • 1-ch Liquid Leak Detection
  • Liquid Leakage detection triggers and audible alarm
  • A mute button to silence the audible alarm
  • Two LED indicators to display the status of the power and the alarm
  • Relay Output for Liquid Leakage Alarm
  • Liquid Leak Detection Cable and Leader Cable can be up to 500 meters
  • Sensitivity adjustable
  • Supports the DCON and the Modbus RTU Protocols

  • Introduction
  • Application
  • Specification
  • Download
  • Get A Quote

Tab 1

The iSN-101 Liquid Leak Detection Module is a low-cost intelligent liquid leak detection device that can be used to directly control Relay Output. No additional conversion module is needed and the iSN-101 can be easily integrated with a variety of monitoring systems to achieve remote alarm and remote device control. The iSN-101 Liquid Leak Detection module can be used to monitor double-core leader cable lengths of up to 500 meters, and can be used with both the extended cable and its included liquid leak detection cable. If liquid is detected, the controller immediately activates the output relay - the normally open, normally closed passive output signal . The module can be easily integrated with other collection hosts connected to the network. The iSN-101 is suitable for real-time leak detection in critical locations, such as computer room base stations, warehouses, libraries, museums and industrial sites, and also for air handling equipment, refrigeration units, liquid containers, or pump tanks, etc., where there is a need to monitor any leakage of the equipment.

When required, communication with the iSN-101 can be programmed based on the Modbus RTU protocol, with the added benefi t that different addresses can be confi gured via hardware to allow for Modbus RTU communication.

Series Model Channel Leader Cable Detection Cable Detection Probe Relay Alarm Interface Mounting
iSN-101

iSN-101
iSN-101 1 - - - Yes RS-485,
Modbus RTU,
DCON
Wall Mount
iSN-101/DIN DIN-rail
iSN-101/S 1 3 m 1 m - Wall Mount
iSN-101/S/DIN DIN-rail
iSN-101/S2 1 3 m 3 m - Wall Mount
iSN-101/S2/DIN DIN-rail
iSN-101/S3 1 - - Yes Wall Mount
iSN-101/S3/DIN DIN-rail
iSN-104
iSN-104
iSN-104 4 - - - - RS-485,
Modbus RTU,
DCON
DIN-rail
iSN-104-E 4 - - - - Ethernet, PoE DIN-rail

Application

Applications
iSN-101/S2

Specification

EMS Protection
EFT (IEC 61000-4-4) ±4 kV for Power
ESD (IEC 61000-4-2) ±8 kV Air for Random Point
LED Indicators
Status 1 as Power Indicator
1 as Alarm Indicator
System
Alarm For both liquid leak detection and cable-break detection.
Buzzer Yes.
Can be muted by a push button.
Relay Output Signal Relay, Form A x1, SPST
0.25 A @ 250 VAC
0.5 A @ 125 VAC
2 A @ 30 VDC
Liquid Leak Detection
Channels 1
Liquid Type Water, 2uS/cm
Sensor Type Cable for line detection
Max. Cable Length 500 meters
Includes liquid leak detection cable and extended cable.
Sensitivity Range 26 KΩ ~ 580 KΩ (rotary switch adjustable)
COM Ports
Ports 1 x RS-485
Baud Rate Software Configuration: 1200 ~ 115200 bps
Data Format (N,8,1), (O,8,1), (E,8,1), (N,8,2)
Protocol Modbus RTU or DCON
Power
Reverse Polarity Protection Yes
Input Range 10 ~ 30 VDC
Consumption 1.5 W Max.
Mechanical
Dimensions (mm) 80 x 70 x 28 (W x L x H)
Installation Wall mount
Cable Length 3m Liquid Leak Detection Cable
3m Extended Cable
Environment
Operating Temperature -25 ~ +75 °C
Storage Temperature -30 ~ +80°C
Humidity 10 ~ 90% RH, Non-condensing

Tab 4